NVS – Pointer Conventional Fire Detection and Alarm Panel

A system which can give fire warning system together with the location information.

It has models with 8, 16, 24, 32, and 48 location capacities.

In total 20 detectors and required number of fire warning buttons might be connected on each detection line.
There are 1 siren which can be activated instantly in case of fire alarm, and 2 dry contact outputs.

There is 1 output with 24 VDC other than the sound and visual warnings in case of an error on the panel.
Detection lines, siren output, and error output are constantly checked against line breakage and line short circuit failures. Line breakage and line short circuit failures that can occur on the lines, cutting of voltage feeding the central electric unit, and battery failures are shown on the LCD display (in Turkish) with sound.

Fire alarm information is given as sound with the buzzer inside the panel and in written on the LCD display to the user when it is taken from the detectors or buttons. Information of more than one alarms coming at the same time are shown alternately on the display.

For the visualization of the detection lines on the screen, names (e.g. 1st floor, 2nd floor, cafeteria, etc.) demanded by the user can be written at the ordering stage.

When requested sirens can be deactivated, buzzer can be turned off, and the required detection lines can be deactivated by means of the buttons on the panel.

Smoke detectors, heat detectors, beam type smoke detectors, flame detectors, fire alarm buttons, flow switches, gas detectors, channel type smoke detectors, phone call module, additional relay module, sirens, flasher sirens can be connected to the panel.

Panel body is manufactured from sheet metal and painted with electrostatic powder coating.
The supply voltage is 220VAC.

In case the supply voltage is cut a failure information is given on the panel side and panel continues its operation by using its internal batteries. When the supply is corrected the panel returns to normal operation and it checks and ensures charging conditions of the batteries.

Panel has one 24VDC/250 mA siren, two 220 V/500 mA contact and one 24VDC/250mA failure outputs.
By means of those outputs alarm sirens, automatic searching devices, ventilation systems, automatic extinguishing systems, remote warning systems etc. devices can be controlled in any case.